Temporary Air Fuel Logistics Calculator

5 min read14 sections

Interactive resource

Use the working tool for this page

This page has a matching worksheet, calculator or comparison resource. It runs in your browser: enter your own measured values and keep the evidence behind every result.

Open resource

The calculator separates machine fuel burn from storage capacity, reserve policy and delivery logistics so that a temporary compressor is not treated as operationally ready simply because its airflow and pressure are adequate.

1. Purpose and Engineering Decision

Temporary compressed air can fail for reasons that have nothing to do with compressor capacity. A diesel compressor may be correctly sized for flow and pressure yet still stop because its onboard tank is too small for the shift pattern, a night refuelling window was missed, a fuel truck cannot reach the workfront, or the fuel plan assumes full-tank volume is fully usable.

It is a logistics calculator, not a combustion or engine-performance model.

Mode

Primary output

Shift fuel plan

Fuel required per shift / day

Tank autonomy

Hours remaining from usable tank volume

Refuelling plan

Refill interval and number of refuels

Delivery plan

Daily / weekly site fuel-delivery requirement

Fleet mode

Combined fuel demand for multiple compressors

Economic mode

Fuel cost + delivery / handling allowance

Scenario mode

Low / base / high burn and runtime cases

2. Fuel-Burn Input Must Match Operating State

Fuel consumption should come from a verified machine curve, measured site data or a supplier/OEM operating estimate at a defined load.

Fuel per Period = Sum(Fuel Rate_i x Time_i)

Operating state

Typical input

Loaded / high demand

L/h at verified load point

Part load

L/h at verified part-load point or measured value

Idle / unloaded

L/h

Stopped

Normally 0 L/h

Warm-up / cool-down

Optional explicit allowance

3. Shift / Daily Fuel Demand

Shift Fuel = Sum(Fuel Rate_i x Hours_i) + Fixed Shift Allowance

Daily Fuel = Sum(Shift Fuel_j)

Fixed allowance may represent warm-up, repositioning, short unlogged idle periods or a user-defined contingency. It must remain visible as an input rather than being hidden inside the fuel rate.

4. Tank Usable Volume

A nominal tank capacity should not automatically be treated as fully usable. The calculator should allow a maximum fill fraction and a minimum retained/reserve fraction.

Usable Tank Volume = Nominal Tank x (Maximum Fill Fraction - Minimum Retained Fraction)

If the machine has a verified manufacturer-defined usable capacity, that value may be entered directly and should take priority over a generic fraction method.

5. Autonomy and Refuelling Interval

Autonomy (h) = Usable Fuel Volume / Average Fuel Burn (L/h)

Refuelling Interval (h) = Autonomy x Operating Availability Factor

The availability factor can be used when the site deliberately refuels before the theoretical tank-empty point. For example, a planner may use only 80% of calculated autonomy to protect against burn-rate variation and late delivery.

6. Reserve Fuel Policy

Reserve Fuel = Planned Consumption over Reserve Window

Reserve should be expressed as an operating window - for example one shift, six hours or one delivery interval - rather than a universal percentage. This makes the result operationally meaningful.

Reserve basis

Use

Hours of operation

Remote workfront / uncertain delivery

One shift

Continuous shutdown or commissioning work

One scheduled delivery interval

Regular tanker route

Percentage of tank

Simple site rule; should still be translated to hours

7. Delivery Quantity and Frequency

Delivery Quantity = Consumption until Next Delivery + Required Reserve - Fuel on Hand

Deliveries per Project = Ceiling(Total Project Fuel / Usable Delivery Quantity)

A delivery plan must also consider tanker capacity, site tank free space, access windows, working-hour restrictions and whether fuel can be transferred while the compressor remains in operation.

8. Input Model

Input group

Field

Validation / note

Machine

Compressor / fleet ID

Required

Operating profile

Hours by load state

Total <= schedule period

Fuel

L/h by operating state

>= 0

Tank

Nominal or verified usable volume

> 0

Tank

Maximum fill fraction

0-1

Tank

Minimum retained fraction

0-1 and < max fill

Planning

Operating availability factor

0-1

Reserve

Reserve hours / shift / %

Explicit method

Project

Days / shifts / hours

Positive

Delivery

Tanker / site delivery quantity

> 0

Delivery

Delivery / handling cost

Optional

Economics

Fuel price per litre

>= 0

Uncertainty

Low / base / high burn factor

Optional

9. Reference Test Case A - One 12-Hour Shift

A temporary compressor operates 8 hours loaded at 32 L/h, 3 hours unloaded at 14 L/h and 1 hour stopped. Add a 10 L fixed shift allowance.

Shift Fuel = (8 x 32) + (3 x 14) + 10 = 308 L

Result

Value

Shift fuel

308 L

Average over 12 h schedule

25.7 L/h

Loaded-share of fuel

256 L

Unload + allowance

52 L

10. Reference Test Case B - Tank Autonomy

The compressor has a 500 L nominal tank. Maximum planned fill is 95% and minimum retained fuel is 15%. Use the average 25.7 L/h from Test Case A.

Usable Fuel = 500 x (0.95 - 0.15) = 400 L

Theoretical Autonomy = 400 / 25.7 = 15.6 h

With an 80% operating-availability factor, planned refuelling interval becomes approximately 12.5 hours. That interval is shorter than theoretical autonomy by design.

11. Reference Test Case C - Four-Compressor Shutdown Fleet

Four compressors have expected daily fuel demands of 620 L, 540 L, 410 L and 350 L. The shutdown lasts 10 days.

Calculated item

Result

Fleet daily fuel

1,920 L/day

10-day project fuel

19,200 L

Average hourly burn over 24 h basis

80.0 L/h

The fleet total should then be checked against site tankage, tanker capacity and the permitted delivery window.

12. Reference Test Case D - Delivery Plan with Reserve

Fleet daily consumption is 1,920 L/day. The site wants two days of operating reserve and receives fuel every three days. Fuel on hand immediately after the previous delivery is 5,000 L.

Required stock for next 3-day interval + 2-day reserve = 5 x 1,920 = 9,600 L

Next Delivery Quantity = 9,600 - 5,000 = 4,600 L

If tanker capacity is lower than the calculated quantity, the logistics engine should split the quantity into multiple deliveries while preserving the required reserve floor.

13. Fuel Cost

Fuel Cost = Total Fuel Volume x Fuel Price per Litre

Total Logistics Cost = Fuel Cost + Delivery Charges + Handling / Pumping Allowance

14. Refuelling Trips and Tanker Capacity

Required Trips = Ceiling(Required Delivery Volume / Tanker Deliverable Volume per Trip)

Deliverable volume per trip may be lower than tanker nameplate capacity because of route limits, compartmenting, site tank free space or a company operating limit. The calculator should use the user-entered deliverable quantity.

15. Multi-Site / Multi-Workfront Planning

Planning level

Required calculation

Machine

Fuel burn by state

Workfront

Machine totals + local reserve

Site

All workfront demand + central storage

Project

Site totals + delivery schedule + contingency

16. Fuel Burn Uncertainty

Actual burn varies with load, ambient condition, engine condition, compressor pressure setting, idling, operator behavior and measurement accuracy. The calculator should therefore allow low/base/high fuel-rate multipliers.

Scenario Fuel = Base Fuel x Burn Multiplier x Runtime Multiplier

Scenario

Example use

Low

Measured efficient operation / shorter runtime

Base

Expected operating plan

High

Heavy loading, extended hours, delivery delay contingency

17. Schedule Risk and Delivery Delay

The calculator may model a delivery-delay window by adding the fuel required to survive the delay to the reserve stock.

Delay Reserve = Average Burn x Maximum Planned Delivery Delay

This is especially useful where access depends on security windows, weather, road condition or shutdown permits.

18. Electric Temporary Air Boundary

19. Confidence Model

Input source

Suggested confidence

Measured fuel meter + controller state / runtime data

High

Verified supplier/OEM fuel curve at matched load

High

Historical project fuel issue records

Medium-High

Rated full-load consumption with estimated load factor

Medium / preliminary

Generic L/h assumption

Low / preliminary

20. Validation and Guardrails

Condition

Required behaviour

Fuel rate < 0

Block calculation

Tank volume <= 0

Block autonomy mode

Max fill <= minimum retained

Block tank calculation

Availability factor <= 0 or > 1

Block interval result

Project duration <= 0

Block project mode

Delivery quantity <= 0

Block trip calculation

Fuel on hand > physical site capacity

Warn / require confirmation

Reserve window exceeds storage capability

Flag infeasible logistics plan

Load-state hours exceed schedule period

Block or request correction

Fuel rate source unmatched to pressure/load

Lower confidence / warning

21. Output Specification

Output

Display rule

Shift / daily fuel

L

Average burn

L/h

Usable tank volume

L

Theoretical autonomy

h

Planned refuelling interval

h

Reserve fuel

L and equivalent operating hours

Project fuel

L

Delivery quantity

L per delivery

Delivery trips

Count

Fuel + logistics cost

Currency

Confidence / warnings

Always visible

Calculators and worked examples

These tools give indicative figures for screening, comparison and for preparing an enquiry. They run in your browser and send nothing. Prices, tariffs and efficiencies shown are example values: replace them with your own. Results are not a performance guarantee or a design certificate; final selection is confirmed by an engineer against the machine data sheet and the site.

Temporary air fuel logistics

Plan diesel supply for a hired diesel-driven compressor.

The worked example below shows the method with fixed numbers. Turn on JavaScript to change the inputs.

Worked example

Inputs
  • Fuel burn at working load (L/h): 35
  • Running hours per day: 16
  • Days per week: 6
  • Usable tank volume (L): 400
  • Diesel price (₹/L) — enter current price: 90
Result
  • Fuel per day: 560 litres
  • Fuel per week: 3,360 litres
  • Tank lasts: 11.4 running hours
  • Refills per week: 8.4
  • Fuel cost per week: ₹ 3,02,400

Method. Fuel per day = burn rate × running hours. Refills per week = fuel per week ÷ tank usable volume. Take the burn rate from the supplier datasheet for the actual load.

What to take from it. Fuel logistics decide whether a hired set runs through the shift. Plan refilling so it never depends on stopping the machine.